ESP Fire Panel in Metal Casing - 4 Zone

Description

  • 4 programmable zones


  • Active end of line monitoring and head removal


  • 30 fire detectors per zone


  • Unlimited number of call points per zone


  • Integral sound alarm button


  • 'Class change' facility


  • Enable/disable security key


  • One man walk test facility


  • Volt free fire change over relay


  • Volt free fault change over relay


  • Individual sounder circuit fault ID


  • Individual zone/sounder isolate


  • BS5839 and EN54 P2/4 compliant


  • CE certified


  • Requires only 1x12v battery


  • Metal casing


Max Detectors per Zone30
Thresholds for Zone Conditions0 - 2 mA (Fault condition) 2 - 6 mA (Normal condition) 6 - 110 mA (Fire condition) 110 mA - Short (Fault condition)
Power
Mains Fail Consumption50mA
Mains Supply230 VAC ± 10%
Standby Supply1 x 7ah 12V S.L.A. Battery
Power Availability0.7 amps
Outputs
Sounder 124V (max 300mA fused)
Sounder 224V (max 300mA fused)
Fault/Fire RelayVolt free 500mA @ 24V (max load)
Auxiliary Output24VDC (300mA fused)
Environment
Working Temperature0 to 40ºC
Storage Temperature-20 to 60ºC
Humidity0 - 95%
Dimensions MAG4P340 x 290 x 100mm
Dimensions MAG4320 x 220 x 80mm
WeightMAG4P - 2.5Kg MAG4 - 3.5Kg
Earn 0 reward points with this purchase